CERTIFICATES

TABLE OF CERTIFICATES

The data described in the following table meet the requirements asked for the Afiti Licof fire resistance laboratory in order to certify metallic fire resistance ducts with E600/120(HO) 500 Single classification

CONDUCTAIRE E600º - 120 Certified systems
System selector Connector type Sheet thickness PDF Report number Maximum dimensions Joint sealing
System 1 UT - 1 1.1 0.6 mm 8247 600 x 500 mm Refractory putty
1.2 0.8 mm 7583-07-33 1200 x 1000 mm
1.3 1.0 mm
1.4 1.2 mm
Extension UT - 1 Ext-056 RES-08-3
System 2 B - 20 2.1 0.6 mm 8118 1200 x 1000 mm Ceramic gasket
2.2 0.8 mm 7660-08-7
2.3* 1.0 mm
2.4* 1.2 mm
Extension B - 20 Ext-055 RES-08-3
System 3 B - 30 3.1 0.6 mm 7537-07-06 1200 x 1000 mm Ceramic gasket
3.2 0.8 mm
3.3 1.0 mm
3.4 1.2 mm
3.5 1.0 mm 7870-08 2000 x 600 mm
Extension B - 30 Ext-006 RES-10
System 4 UT - 3 4.1 0.6 mm 7822 1200 x 1000 mm Ceramic gasket
4.2 0.8 mm
4.3 1.0 mm 7863 2000 x 600 mm
4.4 1.2 mm 7820 2000 x 600 mm
Extension UT - 3 Ext-061 RES/8
System 5 Conducto circular 5.1 desde 0.5 mm 8031-09-5 Ø 80 hasta 1050 Ø Refractory putty
5.2 hasta 1.2 mm 7993-09-5
Extension UT - 3 EST-01 8RES-09

Under these rules we provide a 5 year guarantee of installation.

*Not recommended system for its manufacture.


Other certificates


MECHANICAL STABILITY CERTIFICATE AT 400ºC DURING TWO HOURS




RESISTANCE CERTIFICATE
FLANGE OF 20 AND FLANGE OF 30